Amber Alert represents an aeration problem. It is accompanied by an audible alarm which can be muted if the problem cannot be fixed quickly. First check the 1/8 inch air tube that runs from the Control Panel to the compressor for leaks. Make sure the compressor is turned on and the breaker labeled COMP inside the control panel is in the ON position. If alarm persists, contact us at 830-995-3189.

Red Alert represents a high water alarm. It is accompanied by an audible alarm which can be muted if necessary. If this alarm is on and sprinklers are spraying, stop using water and wait on the water level to drop below the alarm level. If this alarm is on and sprinklers are not spaying, check breaker labeled PUMP inside of the control panel. Turning this break on should fix the problem. If this does not fix the problem please contact us at 830-995-3189.

Both alarms can be silenced by placing their respective switches on the side of the Control Box in the mute position. Please keep switches in the up or run position during normal use. 